Sign In | Join Free | My disqueenfrance.com |
|
Place of Origin : Wuhan Hubei China
Brand Name : Huaying
Certification : ISO
Model Number : HYJB-PC6
MOQ : 1 Set
Price : Negotiable
Packaging Details : Wooden Case
Delivery Time : 7 Working Days
Payment Terms : T/T L/C
Supply Ability : 200 sets per month
Frequency Error : <±0.01Hz
Phase Error : <±0. 2°
Waveform Distortion : <±0.3% (Fundamental Wave)
Time Error : <40µs
Output Frequency : 0~1050Hz
Ambient Temperature : Use Range 0~45℃
6 Phase Relay Protection Tester Secondary Current Injection Test ISO Approve
Product Name:
6 Phase Relay Tester HYJB-PC6
Equipment Description:
This tester with standard 6 phase voltage, 6 phase current output,
voltage 125V/phase, current 30A/phase, 6 phases in parallel can up to 180A.
Digital Signal Processor Microcomputer. Not only test the traditional relays and protectors,
but also test the modern micro computer replays, special for transformer
differential protection and transfer equipments.
Except detecting various relay protection testers ( such as current, voltage, IDMT, power direction, impedance, differential, low-cycle, simultaneous, frequency, DC and time etc) and microcomputer protection, it can also simulate instantaneous, permanent and transformational faults to test from single-phase to three-phase. Moreover, it can finish all kinds of large-scale and complicated checkout work with high automatic level. This will also be convenient to test and scan various protective definite value, to carry out bug playback, to store testing data in the real time, to display vector diagram, to print report online and to test ATS, fast cutting and system shock etc. 6-phase current can conveniently proceed with 3-phase differential motion protective testing, while 12-phase output can be used in ATS testing.
Technical Parameters:
1. AC current source
Current range: 6x (0~30A)/phase, accuracy 0.5%.
6 phase parallel current output: 180A
Phase current working value for allowed long time: 10A
Power: 300VA/phase
Maximum output power of 6 phases in parallel: 900VA
Maximum permitted work time of 6 phases in parallel: 10S
Frequency range: 0~1000Hz; accuracy: 0.001Hz
Harmonic time: 2~20; phase: 0--360°; accuracy: 0.1°
2. DC current source
Current range: 20A / phase, power: 300VA/phase, accuracy:0.5%
3. AC voltage source
Phase voltage output:6x( 0~125V)/phase, accuracy: 0.5%
Line voltage output: 0~250V
Phase voltage / Line voltage output power: 70VA / 100VA
Frequency range: 0~1000Hz accuracy: 0.001Hz
Harmonic time: 2~20; phase: 0--360°; accuracy: 0.1°
4. DC voltage source
Phase voltage output range: 0~±150V accuracy: 0.5%
Line voltage output range: 0~±300V
Phase voltage / Line voltage output power: 90VA / 180VA
5. Switch terminal
Switch input terminals: 8 pairs
Dead contact: 1-20mA, 24V active output inside the device.
Potential flip: 0--6V DC low level
15-250V DC high level
Switch output terminals: 4 pairs, dead contact, rupturing capacity: 110V/2A, 220V/1A
6. Time measurement range
Range: 1ms-9999s; accuracy: 1ms
![]() |
6 Phase Relay Protection Tester Secondary Current Injection Test ISO Approve Images |